Data Sheet

Bulletin 71.1:CS800
14
travel of the relief seat. Since the diaphragm continues
to rise as downstream pressure builds, the diaphragm
lifts off of the relief seat to provide relief operation. The
secondary travel stop for internal relief is not available
on token relieving units. Units with high capacity
internal relief valve have 2-1/2 NPT vent size. See
Figures 10, 12, 14, 16, 18 and 20 for relief capacity.
Token Relief “T” and Low Flow Token
Relief “L”
Type numbers with the “T” or “L” sufx, e.g.,
Types CS800IT and CS800IL provide a low capacity/
token relief. Token relief provides relief from minor
overpressure caused by nicks or dents on the orice
or by thermal expansion of gas in the downstream line.
Token relief also provides a token or signal, in the form
of odor, that an overpressure situation is occurring.
Start-to-discharge values for Token reliefs are found
in Table 5. Maximum discharge capacities for Token
reliefs are found in Figure 8.
Types CS803 and CS823 Integral
True-Monitor™ Operation
Types CS803 and CS823 combine the operation of a
conventional two-regulator wide-open monitor set into
one body, see Figure 5. The Integral True-Monitor is
installed on the inlet side of the body and serves to
control downstream pressure in the situation where the
Primary regulator can no longer regulate downstream
pressure. During normal operation the True-Monitor is
in a wide-open state as its setpoint is set higher than
the primary regulator. See Tables 7 and 8 for guidance
regarding the setpoints of the regulator and associated
Integral Monitor sets. If the downstream pressure
should rise to the setpoint of the True-Monitor due to
loss of pressure control by the primary regulator, the
monitor will assume control and regulate ow to the
downstream system. Internal and external downstream
pressure registration are available. External pressure
registration requires a downstream sensing line. See
the Type TM600 Instruction Manual for additional
details of operation.
If a Token relief is present, the token relief will relieve
a small amount of gas to the atmosphere as an
indication that the Integral Monitor is controlling the
downstream pressure.
Types CS804, CS824 and CS854
Slam-Shut Operation
The Type VSX8 Slam-shut module on the
CS804 Series regulators is a fast acting shutoff
device that provides overpressure (OPSO) or
overpressure and underpressure (OPSO/UPSO)
protection by completely shutting off the ow of gas
to the downstream system. See Tables 12 and 13
for guidance regarding the typical setpoint of the
regulator and associated OPSO and UPSO sets.
The Type VSX8’s actions are independent of the
CS804 Series regulator and of variations to the inlet
pressure. The Type VSX8 provides the option of
internal or external downstream pressure registration.
External registration requires a downstream
sensing line.
The Type VSX8 shutoff disk is normally in the open
(reset) position, see Figure 6. If the downstream
pressure below the slam-shut diaphragm increases (or
decreases) until it reaches the slam-shut setpoint, this
diaphragm moves upward (or downward) to release
the trip mechanism which allows the spring force on
the stem to push the disk against the seat, shutting
off all gas ow. To reset the slam-shut after gas has
been shutoff, refer to Type VSX8 Instruction Manual
(D103127X012) for additional details.
Figure 8. Maximum Discharge Capacity for Token and Low Flow Token Relief
REGULATOR SETPOINT, psig / bar
Discharge Capacity in SCFH / Nm
3
/h at Maximum Operating Outlet
(3 psi / 0.21 bar setpoint) (Specific Gravity Gas = 0.6)
6 / 0.41
150 /
4.02
200 /
5.36
250 /
6.7
300 /
8.04
350 /
9.38
400 /
10.72
450 /
12.06
5.5 / 0.38
4.5 / 0.31
2.5 / 0.17
3.5 / 0.24
1.5 / 0.10
0.5 / 0.03
5 / 0.34
4 / 0.28
3 / 0.21
2 / 0.14
1 / 0.69
0
REGULATOR SETPOINT, psig / bar
Discharge Capacity in SCFH / Nm
3
/h at Maximum Operating Outlet
(3 psi / 0.21 bar setpoint) (Specific Gravity Gas = 0.6)
6 / 0.41
8 /
0.214
10 /
0.268
12 /
0.322
14 /
0.375
16 /
0.429
20 /
0.536
22 /
0.59
24 /
0.643
18 /
0.482
26 /
0.697
5.5 / 0.38
4.5 / 0.31
2.5 / 0.17
3.5 / 0.24
1.5 / 0.10
0.5 / 0.03
5 / 0.34
4 / 0.28
3 / 0.21
2 / 0.14
1 / 0.69
0
Maximum Discharge Capacity for Token Relief
Maximum Discharge Capacity for Low Flow Token Relief