Data Sheet

Bulletin 71.1:CS200
9
Internal Relief
The internal relief provided by the Type CS200IR limits
the total outlet pressure to values shown in Relief
Tables 8, 11, 16, and 21. This internal relief may be
adequate, however, if an additional pressure relief
is required to maintain downstream pressure at the
desired maximum level, an additional relieving or
pressure limiting device should be installed to protect
downstream equipment.
Overpressuring any portion of a regulator or
associated equipment may cause leakage, parts
damage, or personal injury due to bursting of
pressure-containing parts or explosion of accumulated
gas. Regulator operation within ratings does not
preclude the possibility of damage from external
sources or from debris in the pipeline. A regulator
should be inspected for damage periodically and after
any overpressure condition.
Refer to the relief sizing coefcients. Table 3, and the
Capacity Information section to determine the required
relief valve capacity.
Internal Relief Per ANSI B109.4
The ANSI B109.4 standard applies to outlet
setpoints at or below 14-inches w.c. / 35 mbar. At
these conditions the maximum outlet pressure
allowed during relief is 2 psig / 138 mbar. If the
Type CS200IR installation requires conformance
with the ANSI B109.4, then the maximum inlet
pressure allowed per orice is limited to the value
that maintains an outlet below 2 psig / 138 mbar
during relief. Reference applicable relief capacity
curves, Figures 5 through 8, to determine maximum
allowable inlet per orice.
Flows are in SCFH (60°F and 14.7 psia) and Nm³/h
(0°C and 1.01325 bar) of 0.6 specic gravity natural
gas. To determine equivalent capacities for air,
propane, butane, or nitrogen, multiply the capacity
number in the tables by the following appropriate
conversion factor: 0.775 for air, 0.628 for propane,
0.548 for butane, or 0.789 for nitrogen. For gases of
other specic gravities, multiply the given capacity by
0.775 and divide by the square root of the appropriate
specic gravity.
The published capacities were obtained using inlet and
outlet piping the same size as the regulator body size.
Relief Sizing
For Critical Flow:
To determine wide-open flow capacities for relief
sizing of 0.6 specific gravity natural gas at 60°F at
critical pressure drops (absolute outlet pressure
equal to approximately one-half or less than
one-half of the absolute inlet pressure), use the
following formula:
Q= P
1abs
(C
g
)(1.29)
For Subcritical Flow:
If pressure drops are lower than critical (absolute
outlet pressure greater than approximately one-half
the absolute inlet pressure), use the following formula
and convert according to the factors in the preceding
paragraph if necessary:
Q = C
g
P
1
SIN
520
GT
3417
C
1
∆P
P
1
DEG
where:
Capacity Information
Tables 7, 9 to 10, 12 to 15, 17 to 20, and 22 to 32 give
the CS200 Series natural gas regulating capacities at
selected inlet pressures, outlet pressure settings, and
body outlet sizes.
C
1
= C
g
/C
v
(See Table 2)
C
g
= Gas sizing coefcient (See Table 3)
g = Gas specic gravity (air = 1.0)
P
1
= Regulator inlet pressure, psia
∆P = Pressure drop across regulator, psi
Q = Gas ow rate, SCFH
T = Absolute temperature of gas at inlet, °Rankine