Data Sheet
Bulletin 71.1:CS200
14
ORIFICE SIZE REGULATOR SET PRESSURE
MAXIMUM INLET PRESSURE TO KEEP OUTLET PRESSURE AT OR BELOW
(1)(2)
2 psig / 138 mbar 2.5 psig / 0.17 bar
Inch mm Inch w.c. mbar psig bar psig bar
1/8 3.2
14 35
>125 >8.6 >125 >8.6
3/16 4.8 59 4.1 82 5.7
1/4 6.4 28 1.9 40 2.8
3/8 9.5 10 0.69 14 0.97
1. Relief value obtained by disconnecting the lever.
2. 2 psig / 138 mbar is the maximum outlet pressure allowed per ANSI B109.4.
Table 11. Type CS200IR Internal Relief Performance Table for 14-inches w.c. / 35 mbar Setpoint
Figure 6. NPS 1 Body Type CS200IR Typical Relief Performance (Linkage Disconnect) at 14 inches w.c. / 35 mbar Set Pressure
OUTLET PRESSURE, psig / bar
INLET PRESSURE, psig / bar
0 10 / 0.69 20 / 1.4 30 / 2.1 40 / 2.8 50 / 3.4 60 / 4.1 70 / 4.8 80 / 5.5 90 / 6.2 100 / 6.9 110 / 7.6 120 / 8.3
1/8-INCH / 3.2 mm
ORIFICE
3/16-INCH / 4.8 mm
ORIFICE
ANSI B109.4 MAXIMUM
OUTLET PRESSURE
1/4-INCH / 6.4 mm
ORIFICE
3/8-INCH /
9.5 mm ORIFICE
1/2-INCH / 13 mm
ORIFICE
3 /
0.21
2.5 /
0.17
2 /
138 mbar
1.5 /
103 mbar
1 /
69 mbar