Data Sheet
Bulletin 71.1:CS200
11
Figure 5. NPS 1 Body Type CS200IR Typical Relief Performance (Linkage Disconnect) at 7 inches w.c. / 17 mbar Set Pressure
ORIFICE SIZE REGULATOR SET PRESSURE
MAXIMUM INLET PRESSURE TO KEEP OUTLET PRESSURE AT OR BELOW
(1)(2)
1 psig / 69 mbar 2 psig / 138 mbar
Inch mm Inch w.c. mbar psig bar psig bar
1/8 3.2
7 17
36 2.5 >125 >8.6
3/16 4.8 15 1.0 74 5.1
1/4 6.4 6 0.41 36 2.5
3/8 9.5 3 0.21 12 0.83
1. Relief value obtained by disconnecting the lever.
2. 2 psig / 138 mbar is the maximum outlet pressure allowed per ANSI B109.4.
Table 8. Type CS200IR Internal Relief Performance Table for 7 inches w.c. / 17 mbar Setpoint
INLET PRESSURE, psig / bar
OUTLET PRESSURE, psig / bar
10 / 0.69
0
20 / 1.4 30 / 2.1 40 / 2.8 50 / 3.4 60 / 4.1 70 / 4.8 80 / 5.5 90 / 6.2 100 / 6.9 110 / 7.6 120 / 8.3
3 /
0.21
2.5 /
0.17
2 /
138 mbar
1.5 /
103 mbar
1 /
69 mbar
0.5 /
34 mbar
1/8-INCH / 3.2 mm
ORIFICE
3/16-INCH / 4.8 mm
ORIFICE
1/4-INCH / 6.4 mm
ORIFICE
3/8-INCH /
9.5 mm ORIFICE
1/2-INCH / 13 mm
ORIFICE
ANSI B109.4 MAXIMUM
OUTLET PRESSURE