Data Sheet

Bulletin 71.1:CP400
18
Table 18. Types CP403 and CP404 Internal Registration Flow Capacities for 2 psig / 0.14 bar Setpoint
Table 19. Types CP403 and CP404 Internal Registration Flow Capacities for 5 psig / 0.34 bar Setpoint
ACCURACY
SETPOINT + / - 1% ABS SET RANGE
PART NUMBER /
COLOR
2 psig -0.17 psi 0.17 psi 1 to 2 psig
GE30199X012 /
Yellow Stripe
0.14 bar -12 mbar 12 mbar 0.07 to 0.14 bar
ACCURACY
SETPOINT + / - 1% ABS SET RANGE
PART NUMBER /
COLOR
5 psig -0.2 psi 0.2 psi 2 to 5 psig
GE27213X012 /
Orange Stripe
0.34 bar -14 mbar 14 mbar 0.14 to 0.34 bar
CAPACITIES IN SCFH / Nm
3
/h OF 0.6 SPECIFIC GRAVITY NATURAL GAS
Inlet Pressure
Orice Size
3/16 In. / 4.8 mm 1/4 In. / 6.4 mm 3/8 In. / 9.5 mm 1/2 In. / 13 mm 5/8 In. / 16 mm 3/4 In. / 19 mm
SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h
psig bar Body Sizes: NPS 1-1/4, 1-1/2 and 2 / DN 32, 40 and 50
3 0.21 240 6.43 450 12.1 840 22.5 880 23.6 1400 37.5 1300 34.8
5 0.34 450 12.1 740 19.8 1400 37.5 2500 67.0 2500 67.0 3200 85.8
10 0.69 810 21.7 1300 34.8 3000 80.4 4400 118 5600 150 6500 174
15 1.0 980 26.3 1800 48.2 4000 107 6000 161 8200 220 9800 263
20 1.4 1200 32.2 2100 56.3 4700 126 7500 201 8200 220 9800 263
30 2.1 1500 40.2 2700 72.4 6300 169 7500 201 5100 137 5600 150
40 2.8 1900 50.9 3400 91.1 7900 212 4900 131 4400 118 4700 126
50 3.4 2200 59.0 4200 113 7900 212 4400 118 4000 107
60 4.1 2600 69.7 4700 126 4700 126 4400 118
80 5.5 3300 88.4 4700 126 4700 126
100 6.9 4000 107 5100 137
125 8.6 4900 131 5100 137
Blank areas indicate where maximum operating inlet pressure for a given orice size is exceeded.
Gray areas indicate limited capacities due to boost effects.
CAPACITIES IN SCFH / Nm
3
/h OF 0.6 SPECIFIC GRAVITY NATURAL GAS
Inlet Pressure
Orice Size
3/16 In. / 4.8 mm 1/4 In. / 6.4 mm 3/8 In. / 9.5 mm 1/2 In. / 13 mm 5/8 In. / 16 mm 3/4 In. / 19 mm
SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h
psig bar Body Sizes: NPS 1-1/4, 1-1/2 and 2 / DN 32, 40 and 50
10 0.69 630 16.9 1000 26.8 1600 42.9 2700 72.4 3500 93.8 3700 99.2
15 1.0 910 24.4 1400 37.5 3000 80.4 4400 118 5400 145 7400 198
20 1.4 1100 29.5 2000 53.6 4000 107 6000 161 6800 182 7400 198
30 2.1 1500 40.2 2700 72.4 6000 161 6000 161 6800 182 7400 198
40 2.8 1900 50.9 3300 88.4 6000 161 5200 139 6800 182 6300 169
50 3.4 2200 59.0 4000 107 6000 161 4400 118 7200 193
60 4.1 2600 69.7 4700 126 5100 137 4400 118
80 5.5 3300 88.4 6000 161 3700 99.2
100 6.9 4000 107 6700 180
125 8.6 4500 121 8400 225
Blank areas indicate where maximum operating inlet pressure for a given orice size is exceeded.
Gray areas indicate limited capacities due to boost effects.