Each of the four DO circuits contain an optically isolated open source
MOSFET with surge suppressor and are capable of handling 500mA @
30V.
Use jumper W15 to enable power for DIs that are configured for
internal power. The nominal input voltage is 24Vdc at 5mA.
Setting Jumpers
The isolated DI/O module has 15 jumpers you can use to configure
inputs and outputs. See Table 3-29.
Table 3-29. Jumper Assignments: Isolated Vac DI Module
Jumper Purpose Description
W1 Configures DI1 Pins 2-3 & 4-5 installed = Permit external power DI
Pins 1-2 & 3-4 installed = Permit internal source DI
W2-W12 Configures DI2 through DI12
(respectively)
Pins 2-3 & 4-5 installed = Permit external power DI
Pins 1-2 & 3-4 installed = Permit internal source DI
W13 Enables DI/O status LED Pins 1-2 installed = Enables LEDs manually
Pins 2-3 installed = Enables LEDs via software
W14 Programs serial EEPROM
Reserved for factory use only
W15
1
Enables VIN Pins 1-2 installed = Enable VIN
Pins 2-3 installed = Disable VIN
1 Place configuration jumper on pins 1-2 if you configure any DI for internally sourced operation.
Wiring the Module
Figure 3-26 shows field wiring assignments for a locally terminated
isolated DI/O module.