ControlWave Micro Instruction Manual (CI-ControlWave Micro)
3-42 I/O Modules Revised Jun-2013
3.13 Isolated Digital Input/Output (DI/O) Module
Isolated Digital I/O modules provide four isolated DOs that are
externally powered and twelve isolated DIs.
Table 3-28. Isolated (DI/O) Module Characteristics
Type Number
Supported
Characteristics
Isolated Digital
Outputs (DO)
4
Each isolated DO supports/includes:
Externally powered. Supports 500mA
maximum load (nominally powered
from a 10Vdc supply [30Vdc max]_
Surge protection.
Open source MOSFET drives up to
31Vdc at up to 500mA.
500Vdc MOV to chassis and 31Vdc
MOV (across output) protect each DO.
Maximum operating frequency of 20
Hz.
Isolated Digital
Inputs (DI)
12
Each isolated DI supports/includes:
Jumper allows externally powered
single end inputs or internally sourced
dry contact operation.
Nominal input voltage of 24Vdc.
Nominal input current of 5mA.
30 ms filtering.
Isolated DI/O modules consist of a DI/O PCB with two 10-point
terminal block assemblies (for local termination), 14 configuration
jumpers, an LED daughterboard with 16 status LEDs (one for each
point), and a module cover. The isolated DI/O PCB connects with the
backplane using a 36-pin gold-plated card-edge connector.
Detailed Technical
Specifications
For detailed technical specifications, please see our website
http://www.emersonprocess.com/remote.
Configuration
The isolated DI/O module is available in a single configuration (part
number 396804-01-2).
Isolation
Surge suppressors and optocouplers electrically isolate the DI field
circuitry from the module’s bus interface circuitry.
When configured for use in dry contact applications, all DIs use a built-
in +21Vdc field power supply. This is an isolated supply powered by
the output of the +VIN power source originating on the PSSM. Use
jumper W15 to enable or disable the +21Vdc field power supply.