Revised Jun-2013 I/O Modules 3-41
Table 3-27. Jumper Assignments: Isolated Vac DI Module
Jumper Purpose Description
W1 Enables DO status LED Pins 1-2 installed = Enables LEDs manually
Pins 2-3 installed = Enables LEDs via software
Wiring the Module
Figure 3-25 shows field wiring assignments for a locally terminated
relay isolated Vac/Vdc DO module.
P2
TB1
TB2
P1
LED Board
Connector
NOTE:
A Relay Isolated Vac/Vdc DO Module
cannot be installed into Slot #1 of a
Control MICRO
I/O Expansion Chassis!
Wave
1
39
2
A
C/DC
DO Module
LED
A
ssignments
DO1
DO2
DO3
DO4
DO5
DO6
DO7
DO8
W1
LED Enable
1-2 = Enable LEDs Manually
2-3 = Enable LEDs via Software
1
TB1
TB
2
NO_IN1
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
NO_IN2
N/C
NO_OUT3
NO_IN5
NO_IN6
N/C
NO_OUT7
NO_OUT1
NO_OUT2
N/C
NO_IN3
NO_IN4
NO_OUT4
N/C
NO_OUT5
NO_OUT6
NO_IN7
NO_IN8
NO_OUT8
DO1 DO2
DO3
DO4
DO5 DO6 DO7 DO8
FIELD
CIRCUITRY
AC/DC DO MODULE
Field
TB
2
1
NO_IN1
NO_OUT1
Figure 3-25. Relay Isolated Vac/Vdc DO Module Wiring (Local Termination)
Software Configuration
To use data from a Relay Isolated Vac/Vdc Digital Output module you
must add a CWM_DO16 board in ControlWave Designer’s I/O
Configurator, and then configure it. See the ControlWave Designer
Programmer's Handbook (D5125) for more information. That same
manual includes an I/O Mapping section that describes, for advanced
users, the I/O map for this module.