Instruction manual
ControlWave Micro Instruction Manual (CI-ControlWave Micro)
Revised Jun-2013 I/O Modules 3-33
Table 3-23. Jumper Assignments: Non-isolated MI/O Module
Jumper Purpose Description
W1
1
Configures optional AO for
voltage or current output
Pins 1-2 installed = Sets AO for current output
Pins 2-3 installed = Sets AO for voltage output
W2 Configures optional AO for
voltage or current output
Pins 1-2 installed = Sets AO for voltage output
Pins 2-3 installed = Sets AO for current output
W3 Enables DI/DO status LEDs Pins 1-2 installed = Enables LEDs manually
Pins 2-3 installed = Enables LEDs via software
W4 Enables HSC status LEDs Pins 1-2 installed = Enables LEDs manually
Pins 2-3 installed = Enables LEDs via software
W5 & W6 Controls HSC1 Current Pins 1-2 installed = Permits additional 2 mA load
Pins 2-3 installed = Permits 200 uA source; no 2 ma load
W7 & W8 Controls HSC2 Current Pins 1-2 installed = Permits additional 2 mA load
Pins 2-3 installed = Permits 200 uA source; no 2 ma load
W9 & W10 Configures HSC1 and HSC2
debounce (respectively)
Pins 1-2 installed = Enables HSC debounce
Pins 2-3 installed = Disabled HSC debounce
W11-W16 Configures DI1 through DI6
current (respectively)
Pins 1-2 installed = Sets 2 mA source current
Pins 2-3 installed = Sets 60 uA source current
W17-W22 Select DI/O1 through DI/O6
points (respectively)
Pins 1-2 installed = Sets digital input operation
Pins 2-3 installed = Sets digital output operation
W23-W26 Configures AI1 through AI4
(respectively)
Pins 1-2 installed = 4–20 mA AI (250Ω resistor in)
Pins 2-3 installed = 1–5 Vdc AI
W27
2
Selects AO Voltage Pins 1-2 installed = N/A
Pins 2-3 installed = External Field Voltage (TB2-9)
W28 Enables HSC Circuitry Pins 1-2 installed = Enable (power) HSC circuit
Pins 2-3 installed = Disable HSC circuit
1 W1 jumper located on optional AO daughterboard.
2 Set W27 always to pins 2-3.
Wiring the Module
Figure 3-19 shows field wiring assignments for a locally terminated
MI/O module. Figure 3-20 shows field wiring assignments for a
remotely terminated MI/O module.