Instruction manual
ControlWave Micro Instruction Manual (CI-ControlWave Micro)
3-32 I/O Modules Revised Jun-2013
3.10 Non-isolated Mixed I/O (MI/O) Module
Non-isolated Mixed I/O (MI/O) modules provide up to six individually
field configurable DI/Os, four AIs, two HSC Inputs and, optionally, one
AO.
MI/O modules consist of an MI/O PCB with two 10-point terminal
block assemblies (TB1 and TB2 for local termination) or two 14-pin
mass termination headers (P2 and P3 for remote termination), 28
configuration jumpers, and a module cover. The MI/O PCB connects to
the backplane using a 36-pin gold-plated card-edge connector.
Note: I/O circuitry is identical to circuitry used on other I/O modules.
HSC inputs have surge suppression, bandwidth limiting and 20
microsecond (50kHz) filtering. You can individually field-configure
HSC inputs for 2mA or 200uA (low power) operation. Each input of the
HSCI Module is configured as a 16-bit high-speed counter.
Detailed Technical
Specifications
For detailed technical specifications, please see our website
http://www.emersonprocess.com/remote.
Optional AO
Optionally, certain configurations of MI/O modules can also support
one externally powered (VEXT = 11–30 Vdc) analog output.
AO circuitry consists of a 12-bit resolution Digital-to-Analog Converter
(DAC).
Configurations
The non-isolated Mixed I/O (MI/O) module (general part number
396630-XX-X) has the following configurations:
Table 3-22. Mixed I/O Module Configurations
Part Number I/O Included Termination
Connector
Notes
396897-01-0
4AI, 2HSC, 6DI/DO local includes LED daughterboard
396897-02-9
4AI, 2HSC, 6DI/DO
& 1AO (on daughterboard)
local includes LED daughterboard
396897-03-7
4AI, 2HSC, 6DI/DO remote includes LED daughterboard
396897-04-5
4AI, 2HSC, 6DI/DO
& 1AO (on daughterboard)
remote includes LED daughterboard
Setting Jumpers
MI/O modules have 28 jumpers you can use to configure each input or
output. See Table 3-23.