3-26 I/O Modules Revised Jun-2013
Table 3-18. Isolated Analog Input Module Configurations
Part Number Termination Connector Notes
396604-03-0
local
396604-04-8
remote
Setting Jumpers
AI modules have jumpers you can use to configure each of the eight
AIs. You can individually configure AI for 4–20 mA, 1–5 Vdc, or 0–
10 Vdc isolated operation or internally sourced 4–20 mA non-isolated
operation. See Table 3-19 for settings.
Table 3-19. Jumper Assignments: Isolated AI Module
Jumper Purpose Description
W1 – W8 Configures AI1 through AI8
(respectively)
Voltage Input AIs use two dual-pin jumpers
Isolated Current AIs use three dual-pin connectors
Internally sourced AIs use four dual-pin jumpers
See Figure 3-15 and Figure 3-16 for examples of how to
use these jumpers.
W9 Programs Serial EEPROM
Reserved for factory use only
Wiring the Module
Figure 3-15 shows terminal assignments for a locally terminated AI
module; Figure 3-16 shows terminal assignments for a remotely
terminated AI.