Instruction manual

ControlWave Micro Instruction Manual (CI-ControlWave Micro)
3-18 I/O Modules Revised Jun-2013
Table 3-11. Non-Isolated AI/O Module Configurations
Part Number Termination
Connector
Notes
396568-01-7:
local
396568-02-5:
remote
Each non-isolated AI module (general part number 396569-XX-X)
consists of a PCB with six AIs and comes with a module cover. There
are two configurations:
Table 3-12. Non-Isolated AI Module Configurations
Part Number Termination Connector Notes
396569-01-3:
local
396569-02-1:
remote
Cable Shields
Connect cable shields associated with AI wiring to the ControlWave
Micro’s housing ground. Multiple shield terminations require that you
supply a copper ground bus (up to a #4 AWG wire size) and connect it
to the housing’s ground lug.
This ground bus must accommodate a connection to a known good earth
ground (in lieu of a direct connection from the ground lug) and to all AI
cable shields. Shield wires should use an appropriate terminal lug.
Secure them to the copper bus using industry rugged hardware
(screw/bolt, lock washer, and nuts).
Setting Jumpers
AI/O and AI modules have jumpers you can use to configure each of
the six AIs. You can individually configure AIs for 1–5 Vdc or 4–20
mA operation. See Table 3-13.
Table 3-13. Jumper Assignments: Non-isolated AI/O and AI Module
Jumper Purpose Description
JP1-JP6 Configures AI1 through AI6
(respectively)
Pins 1-2 installed = 4-20 mA AI
Pins 2-3 installed = 1-5 V AI
JP7
1
AO1 Field Output Pins 1-2 installed = 4-20 mA AO
Pins 2-3 installed = 1-5 V AO
JP8
1
AO2 Field Output Pins 1-2 installed = 4-20 mA AO
Pins 2-3 installed = 1-5 V AO
JP9
1
AO1 Calibration Test Pins 1-2 installed = 1-5 V AO
Pins 2-3 installed = 4-20 mA AO
JP10
1
AO2 Calibration Test Pins 1-2 installed = 1-5 V AO
Pins 2-3 installed = 4-20 mA AO
JP1 Configures ISP Connector
Reserved for factory use only
W1 Programs Serial EEPROM
Reserved for factory use only
1 Configuration for JP7 and JP9 must match (that is, both 1-5 V or 4-20mA)
Configuration for JP8 and JP10 must match (that is, both -5 V or 4-20mA)