Instruction manual

ControlWave Micro Instruction Manual (CI-ControlWave Micro)
Revised Jun-2013 I/O Modules 3-17
3.6 Non-isolated Analog Input/Output & Analog Input Module
Non-isolated Analog Input/Output (AI/O) modules support six
externally sourced 4–20mA or 1–5 Vdc single-ended analog inputs and
optionally, two independently configurable 4–20 mA or 1–5 Vdc analog
outputs. Non-isolated Analog Input (AI) modules are identical to
AI/O modules but have a depopulated AO section.
AI/O modules consist of an AI/O PCB with two 10-point terminal block
assemblies (for local termination) or two 14-pin mass termination
headers (for remote termination), 12 configuration jumpers, and a cover
assembly. The AI/O module connects with the backplane using a 36-pin
gold-plated card-edge connector.
Table 3-10. Non-Isolated AI/O and AI Module General Characteristics
Type Number
Supported
Characteristics
Analog Inputs
(AI)
6 on AI/O
Module
6 on AI
Module
Each AI supports/includes:
Jumper to configure input for either 4–
20mA or 1–5 Vdc
Signal conditioning that provides 2 Hz
low pass filter
Transorb for surge suppression
Analog to Digital converter
Analog Outputs
(AO)
2 on AI/O
Module
None on AI
Module
Each AO supports/includes:
Jumper to configure output for either 4–
20mA or 1–5 Vdc
maximum external load to the 4–20mA
output of either 250 ohms with an
external 11V power source or 650
ohms with an external 24V power
source.
maximum external load current to the
1–5 Vdc output is 5 mA with an
external 11-30 V power source.
AO operation requires an 11–30Vdc
power source connected to the VEXT
terminal of the AI/O module.
Detailed Technical
Specifications
For detailed technical specifications, please see our website
http://www.emersonprocess.com/remote.
Configurations
Each non-isolated AI/O module (general part number 396568-XX-X)
consists of a PCB with six AIs, 2 AOs, and comes with a module
cover. There are two configurations: