Revised Jun-2013 I/O Modules 3-15
Part Number Termination Connector Notes
396567-04-5:
remote Includes LED
daughterboard.
Setting Jumpers
DI/O modules provide 12 individually field configurable DIs and 4
non-configurable externally powered DOs.
Using configuration jumpers W1 through W12, you can set each DI
individually to provide either a 2 mA or 60 uA source current. Table 3-9
details jumper settings.
Table 3-9. Jumper Assignments: Non-isolated DI/O Module
Jumper Purpose Description
W1-W12 Configures DI1 through DI12
(respectively)
Pins 1-2 installed = 2mA Source Current
Pins 2-3 installed = 60uA Source Current
W13 Enables LEDs Pins 1-2 installed = allows manual enabling of LEDs
Pins 2-3 installed = allows software enabling of LEDs
W14 Programs Serial EEPROM
Reserved for factory use only
Wiring the Module
Figure 3-9 shows the terminal block assignments for a locally
terminated DI/O module. Figure 3-10 shows the terminal block
assignments for a DIN-rail mounted remotely terminated DI/O module.
Figure 3-9. Non-isolated DI/O Module (Local Termination)