Revised Jun-2013 I/O Modules 3-11
function as follows:
Table 3-6. Jumper Assignments: Isolated DO Module
Jumper Purpose Description
WI Configures DI1 Pins 1-2 installed = Manually enables status LEDs
Pins 2-3 installed = Software enables status LEDs
See Figure 3-6 for the location of this jumper.
W2 Programs serial EEPROM
Reserved for factory use only
Wiring the Module
Figure 3-6 shows field wiring assignments associated with a locally
terminated DO module; Figure 3-7 shows field wiring assignments
associated with remotely terminated DO modules. Figure 3-8 shows a
remote termination module with built-in discrete relay modules.
Figure 3-6. Isolated DO Module (Local Termination)