3-6 I/O Modules Revised Jun-2013
source originating on the Power Supply/Sequencer module (PSSM).
Setting Jumpers
Set configuration jumpers W1 through W19 according to Table 3-3.
Use jumper W19 (see Figure 3-3) to enable or disable the +21 Vdc
field power supply.
Note:
Jumpers W1 through W12 and W15 through W19 only apply to
24V DI Modules.
Table 3-3. Jumper Assignments: Isolated DI Module
Jumper Purpose Description
WI Configures DI1 Pins 2-3 & 4-5 installed = External Power DI
Pins 1-2 & 3-4 installed = Internal Source DI
W2-W12 Configures DI2 through DI12
(respectively)
Same as W1
W13 Enables LEDs Pins 1-2 installed = allows hardware to enable LEDs
Pins 2-3 installed = allows software to enable LEDs
W14 Programs Serial EEPROM
Reserved for factory use only
W15 Configures DI13 Same as W1
W16 Configures DI14 Same as W1
W17 Configures DI15 Same as W1
W18 Configures DI16 Same as W1
W19
1
Enables VIN Pins 1-2 enable VIN
Pins 2-3 disable VIN
1 You must install a jumper on pins 1-2 of W19 to configure any DI for internally sourced operation.
Wiring the Module
Figure 3-3 shows field wiring assignments associated with locally
terminated DI modules; Figure 3-4 shows field wiring assignments
associated with remotely terminated DI modules. Figure 3-5 shows an
optional remote termination module with built-in discrete relay module
that supports input from 120 Vac DIs. The special remote termination
module (with built-in discrete relay module) interfaces with an
externally sourced DI module.