Instruction manual
ControlWave Micro Instruction Manual (CI-ControlWave Micro)
2-26 Installation Revised Jun-2013
(Looking into Connector Intf. Side of P1)
Pin 1 (Wht/Grn Stripe) to Pin 1 = DCD
Pin 2 (Wht/Blu Stripe) to Pin 6 = DSR/RX+
Pin 3 (Blu/Wht Stripe) to Pin 2 = RXD/RX-
Pin 4 (Grn/Wht Stripe) to Pin 7 = RTS
Pin 5 (Wht/Org Stripe) to Pin 3 = TXD/TX-
Pin 6 (Wht/Brn Stripe) to Pin 8 = CTS
Pin 7 (Orn/Wht Stripe) to Pin 4 = DTR/TX+
Pin 8 (Brn/Wht Stripe) to Pin 5 = GND
P1
8-Pin
RJ45
Plug
9-Pin Male
“D” Connector
P2
CW
(COM3)
or
CWEXP
(COM5/6)
(
Lookin
g
into Wire Terminal Side of P2
)
Figure 2-19. Full-duplex and Half-duplex Cable
RS-232 Cable
Guidelines
Observe the following guidelines when constructing RS-232
communication cables:
Ensure that DCD is high to transmit (except when dialing a modem)
Verify that each RS-232 transceiver has one active receiver while
disabled (in power down mode); connect the DCD signal to the
active receiver.
Set CTS to high to transmit.
If the port is set for full-duplex operation, RTS is always ON.
Ensure that DTR is always high when port is active; DTR enables
RS-232 transceivers.
Note: Control DTR using the PORTCONTROL function block and
the _Pn_AUTO_DTR system variable in your ControlWave
project. If you turn DTR off through these mechanisms, the
port remains off, even though hardware is fully configured.
When port is set for half-duplex operation, CTS must go low after
RTS goes low.
All RS-232 comm ports support RTS, DTR, CTS, DCD, and DSR
control signals.
All RS-232 comm port I/O signals are protected by surge protectors.
2.4.4 Connections to RS-485 Serial Port(s) on CPU or ECOM
Modules
The RS-485 port supports local network communications to multiple
nodes up to 4000 feet away.
Your CPU module includes one RS-485 port.
If you require additional RS-485 ports, you can purchase an optional
expansion communication module that includes one or two RS-485
ports. The ControlWave Micro can support up to two expansion
communication modules, for a total of up to four additional RS-485
ports beyond the one on the CPU module. Expansion communication
modules reside in slot #3 and slot #4.
RS-485 COM
Port Names and
Connectors
RS-485 COM ports are assigned names based on their location in the
ControlWave Micro.