Revised Jun-2013 Installation 2-25
Figure 2-17. Full-duplex and Half-duplex Cable
Use the half-duplex cable (shown in the bottom part of Figure 2-17)
when connecting the ControlWave Micro to another ControlWave series
unit (again, with the exception of the CW_10/30/35).
When communicating with a Network 3000 series RTU 3305, RTU
3310, DPC 3330, or DPC 3335 or CW_10/30/35, you must use one of
the cables shown in Figure 2-18.
3 = TXD
7 = RTS
8 = CTS
4 = DTR
2 = RXD
1 = DCD
5 = GND
P2
Full-duplex
Cable
(PPP Protocol
)
Half-duplex
Cable
CW Micro
3305/3310/3330/3335/CW_10/30/35
9-Pin Male
“D” Connector
P1
3 = TXD
7 = RTS
8 = CTS
4 = DTR
2 = RXD
1 = DCD
5 = GND
2 = TXD
6 = CTS
7 = DCD
5 = RTS
4 = RXD
1 = DTR
9 = GND
To P2 Pin-2
To P2 Pin-3
To P2 Pin-5
CW Micro
9-Pin Female
“D” Connector
9-Pin Female
“D” Connector
P2
3305/3310/3330/3335/CW_10/30/35
9-Pin Male
“D” Connector
P1
9= GND
7 = DCD
6 = CTS
4 = RXD
2 = TXD
1 = DTR
5 = RTS
To P2 Pin-5
To P2 Pin-4
To P2 Pin-3
To P2 Pin-2
To P2 Pin-1
Figure 2-18. Full-duplex and Half-duplex Cable
When interfacing to the COM3 port of a ControlWave, or the COM5 or
COM6 port a ControlWaveEXP unit, use the cable presented in Figure
2-19 along with the cable shown in Figure 2-17 or Figure 2-18.