Instruction manual
ControlWave Micro Instruction Manual (CI-ControlWave Micro)
Revised Jun-2013 Installation 2-19
Figure 2-15. CPU Module with Two Serial and Two Ethernet Ports
2.4.1 Setting Jumpers on the CPU Module
Each CPU module contains a number of jumpers (labeled with JPn)
when n in the jumper number. See Figure 2-13, Figure 2-14, or Figure
2-15) to locate the jumpers.
Note: When present, jumpers 1, 2, 3, 5, 6, and 9 (JP1, JP2, JP3, JP5,
JP6, and JP9) are reserved for factory use only. Do not alter
these jumpers from their factory settings.
Jumper 4 (JP4) enables the Idle and Status LEDs on the PSSM. It
comes enabled from the factory. (We recommend you leave these
LEDs enabled during initial installation and setup. If power
conservation is an issue, you can disable these LEDs by removing
the jumper.)
Jumper 7 (JP7) enables the Communication Port Status LEDs on the
CPU module. It comes enabled from the factory. We recommend