Instruction manual
ControlWave Micro Instruction Manual (CI-ControlWave Micro)
2-8 Installation Revised Jun-2013
2.2.2 Mounting the Housing
You can mount base or expansion housings to a panel or a wall. When
mounting one of these units to a panel or wall, place it according to the
following guidelines:
Ensure that the front of the ControlWave Micro is visible and
accessible for service (for example, so you can easily install or
remove modules).
Use the mounting holes provided in the base and expansion
housings (see Figure 2-2 through Figure 2-7).
Remove the base housing and any applicable expansion housings from
their cartons and install them at the assigned work site.
Note: If you are attaching an expansion housing to a 4-slot or 8-slot
base housing, remove the three bus terminators JP2, JP3, and
JP4 (see Figure 2-8) from the backplane on the 4-slot or 8-slot
base housings. You also may need to remove the paper label
over the connector on the right back edge of the base housing.
Figure 2-8. JP2, JP3, and JP4 Jumpers on Base Housing
Face the housings and mount the base housing on the left and the
expansion housing on the right so that the connector on the right back
edge of the base housing (P10) seats firmly with the connector on the
left back edge of the expansion housing (P9).
JP2, JP3, &
JP4 jumpers