5-26 Service & Troubleshooting Revised Jun-2013
Once you complete the core updump, set the CPU module’s switch
SW2-1 to ON (Watchdog Enabled) and SW2-4 to OFF (Core Updump
Enabled).
Additionally, if the PSSM has a mode switch, set switch SW1-1 to open
(right) and SW1-2 to closed (left). If the PSSM has a Run/Remote/Local
switch, set it to Local.
With these switches set, power up the Micro and recommence standard
operations.