Revised Jun-2013 Service & Troubleshooting 5-19
Port Module Default Configuation
COM11 ECOM Type 1 Modem port
ECOM Type 2 RS-485: 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol.
You can connect an optional Ethernet port (situated on the CPU
module) directly or via a network to a PC equipped with an Ethernet
port (see Section 2.4.5).
Before starting the WINDIAG program, place any critical processes the
Micro is handling under manual control. You cannot run WINDIAG
while the Micro is running applications. Set the CPU modules switches
SW2-3 and SW2-8 to OFF, and perform the following steps:
1. Start the NetView program in OpenBSI with your current
network NETDEF file. A menu displays (similar to the one in
Figure 5-11):
Figure 5-11. NetView
2. Select Start >Programs > OpenBSI Tools >Common Tools >
Diagnostics. The Main Diagnostics menu (Figure 5-12)
displays.