Instruction manual

ControlWave Micro Instruction Manual (CI-ControlWave Micro)
Revised Jun-2013 Service & Troubleshooting 5-11
Module LED Name LED Color Function
9)
MI/O DI INPUT (6 LEDs, 1 per
point)
Red LED ON = Input is present
LED OFF = Input not present (see Figure 5-9)
MI/O DI INPUT (6 LEDs, 1 per
point)
Red LED ON = Output is ON (see Figure 5-9)
MI/O HSC INPUT (2 LEDs, 1 per
point)
Red LED ON = Input activity on input is present
LED OFF = No activity on input (see Figure 5-
9)
IDI (Vac) INPUT (8 LEDs, 1 per point) Red LED ON = Input is present
LED OFF = Input not present (see Figure 5-9)
IDO
(Vac/dc)
OUTPUT (8 LEDs, 1 per point) Red LED ON = Output is ON (see Figure 5-9)
1
Radio or modem with Type 1 comm board only
PSSM System
Status LED
Codes
As the Micro runs its application, status codes post to the six LEDs on
the PSSM. Table 5-2 provides activity descriptions of the LEDs;
Figure 5-5 shows what the LEDs look like for each hex code.
Table 5-2. System Status LED Codes on PSSM
Status in
Hex
LED 6
ED 5
LED 4
LED 3
LED 2
LED 1
Activity Indicator
00 0 0 0 0 0 0 Application Running
01 0 0 0 0 0 1 Unit in Diagnostic Mode
03 0 0 0 0 1 1 Unit Running Diagnostics
04 0 0 0 1 0 0 Flash XSUM Error
05 0 0 0 1 0 1 Error Initializing Application Device
07 0 0 0 1 1 1 Flash Programming Error
08 0 0 1 0 0 0 Using Factor Defaults (flashed at start)
09 0 0 1 0 0 1 Battery Failure Detected (flashed at
startup)
0A 0 0 1 0 1 0 Currently Loading the Boot Project
0B 0 0 1 0 1 1 System Initialization in Progress
10 0 1 0 0 0 0 Waiting in Recovery Mode
11 0 1 0 0 0 1 Error Testing SDRAM
12 0 1 0 0 1 0 Error Testing SRAM
20 1 0 0 0 0 0 Application Loaded
28 1 0 1 0 0 0 Stopped at Break Point
30 1 1 0 0 0 0 No Application Loaded
38 1 1 1 0 0 0 Running with Break Points
3B 1 1 1 0 1 1 Waiting for a Power-down (after NMI)
3E 1 1 1 1 1 0 Waiting for Updump to be Performed
3F 1 1 1 1 1 1 Unit Crashed (Watchdog Disabled)