HyperTerminal menu bar click Transfer > Send File (see
Figure 5-2).
Figure 5-2. HyperTerminal (Ready to Download)
8. In the Send File dialog box (see Figure 5-3), select 1KXmodem
for the protocol, enter the filename of the appropriate .bin file in
the format “CWMxxxxx.bin” (where xxxxx varies from release to
release) and click Send to start the flash upgrade (see Figure 5-
4). When you see the HyperTerminal Mode Menu again, it
means the download has completed.
9. Exit HyperTerminal and power down the ControlWave Micro. If
desired, you can disconnect the null modem cable between the
ControlWave Micro and the PC.
10. Set the PSSM’s Mode Switch (SW1) for Local Mode, i.e., SW1-1
in the OPEN (Right) position and SW1-2 in the CLOSED (Left)
position or if CPU Module Switch SW1-3 was set for Recovery
Mode, set it to the OFF position (OFF = Recovery Mode
Disabled).
11. Restore power to the ControlWave Micro.