Instruction manual

ControlWave Micro Instruction Manual (CI-ControlWave Micro)
4-8 Operation Revised Jun-2013
Zip Option Description
Zip FW-Libraries
This includes firmware libraries, such as
ACCOL3.FWL in your zwt.
Zip Pagelayouts
This includes pagelayout information for
printing your project, as well as graphical
elements used in certain 1131 languages.
5. Click Zip and a progress bar displays the percent complete of the
zipping process.
6. When the zip process completes, you’ll see a message box reporting
successful completion. Click OK.
7. Copy the resulting zwt file to backup media (CD-ROM, thumb
drive, etc.) If you ever need to restore the project, just open the zwt
file in ControlWave Designer, load libraries as needed, then compile
the project and download it into the ControlWave.
4.5.2 Saving Flash Configuration Parameters (*.FCP)
You must establish communications with the ControlWave Micro using
NetView, LocalView, or TechView before you can run the Flash
Configuration utility.
Note: For detailed information on using the Flash Configuration utility,
see Chapter 5 of the OpenBSI Utilities Manual (D5081).
1. Start the Flash Configuration utility. To do this in NetView or
LocalView, right-click on the icon for this ControlWave and
choose RTU > RTU Configuration Parameters.
To do this in TechView, click Operations > Access Flash
Parameters or click the Access Flash icon
.