4-4 Operation Revised Jun-2013
Port PCB Default Configuration
ECOM Type 2 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM11 ECOM Type 1 Modem port
ECOM Type 2 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
Notes:
You can re-enable the factory default comm. settings at any time by
setting switch SW2-3 on the CPU module to “OFF.”
If you set both SW2-3 and SW2-8 to “OFF” all serial ports
(including COM1) become 9600 baud/BSAP. This is used for
diagnostics mode.
For information on communication cables see Chapter2.
Ethernet
Using an optional Ethernet port (located on the CPU module), you can
connect either directly or through a network to a PC equipped with an
Ethernet port.
Your ControlWave Micro may include 0, 1, or 2 Ethernet ports,
depending upon the type of CPU module. If Ethernet port(s) are
present, the factory pre-configures initial IP addresses and masks, as
follows:
ETH1 IP Address: 10.0.1.1 IP Mask: 255.255.255.0
ETH2 IP Address: 10.0.2.1 IP Mask: 255.255.255.0
Because each unit that ships from the factory has these addresses
initially pre-programmed, you should only use these addresses for
“bench” testing and configuration. You must change these addresses
before putting ControlWave units on an actual network, since an
address conflict would exist as soon as you place the second
ControlWave unit online.
4.3.2 Changing Port Settings
You change port settings (baud rate, port type, IP address, and so on)
using the Flash Configuration utility.
You must establish communications with the ControlWave Micro using
NetView, LocalView, or TechView before you can run the Flash
Configuration utility.
Note: For detailed information on using the Flash Configuration utility,
see Chapter 5 of the OpenBSI Utilities Manual (D5081).
Caution
When you change the baud rate for a port, the baud rate changes as
soon as you write the flash file changes to the RTU, and do not require