Instruction manual

ControlWave Micro Instruction Manual (CI-ControlWave Micro)
Revised Jun-2013 Operation 4-3
Figure 4-3. Mode Switch
4.3 Communicating with the ControlWave Micro
You communicate to the ControlWave Micro by connecting a cable
between a port on your PC workstation and one of the ControlWave
Micro ports.
The port at the PC workstation must match the configuration of the
ControlWave Micro port.
4.3.1 Default Comm Port Settings
As delivered from the factory, ControlWave Micro communication
ports have default settings. Table 4-1 details these defaults.
Table 4-1. Default Comm Port Settings (by PCB)
Port PCB Default Configuration
COM1 CPU Ships from factory at RS-232; 115.2 Kbps using BSAP. Once
the default switch is OFF, a factory default of IP Point-to-Point
protocol (PPP) at 115,200 applies.
COM2 CPU RS-232; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM3 CPU RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM4 ECOM Type 1 or Type
2
RS-232; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM5 ECOM Type 1 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
ECOM Type 2 RS-232; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM6 ECOM Type 1 Not applicable
ECOM Type 2 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM7 ECOM Type 1 Not applicable
ECOM Type 2 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM8 ECOM Type 1 or Type
2
RS-232; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM9 ECOM Type 1 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
ECOM Type 2 RS-232; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM10 ECOM Type 1 Radio port