Figure 2-38. IEC62591 Module – Connecting Termination Jumpers
Software Configuration
After you configure a wireless network for your devices, you need to
configure your ControlWave project to access the interface module,
and through it, the wireless network.
To do this, you either need to modify the IEC62591 example program
in ControlWave Designer to meet the needs of your application, or you
need to copy all the POUs, structures and variables associated with the
example program into an existing project.
In your ControlWave project you must specify the network ID and join
key for the network, which are parameters to the IEC62591 function
block. You also need to specify the long tag name associated with each
wireless device and set its flag for commissioning. In addition you
must specify structure sizes based on the maximum number of wireless
devices to include in your network.
See Chapter 3 of the ControlWave IEC62591 Wireless Interface
Instruction Manual for information on modifying the IEC62591
example program.
For detailed information on configuring the IEC62591 function block,
which is used in the example program, refer to the online help within
ControlWave Designer.
Termination Jumpers