Instruction manual
ControlWave Micro Instruction Manual (CI-ControlWave Micro)
3-62 I/O Modules Revised Jun-2013
Figure 3-36. IEC62591 Interface Module
Connection
You can install the IEC62591 interface module assembly in an open
I/O slot in the ControlWave Micro except, due to a mechanical
restriction, it cannot reside in the last slot of any housing.
You must connect an RS-485 cable between the RS-485 port on the
module, and the Smart Wireless Field Link. This requires a Belden 2-
twisted pair cable.Table 3-41 shows connections for the twisted pair
cable. You must also connect termination jumper wires as shown in
Figure 2-38.
Table 3-41. RS-485 Cable Connections
Smart Wireless
Field Link
IEC62591 Module
A(+) A
B(-) B
POWER - GND
POWER + PWR