Instruction manual

ControlWave Micro Instruction Manual (CI-ControlWave Micro)
Revised Jun-2013 I/O Modules 3-59
Figure 3-35. Switches and Jumpers on the HART/BTI Interface Module
Caution
Settings for SW3 and SW4 must be consistent with the I/O
configuration of the corresponding channels in ControlWave
Designer. To find the location of the switches on the board, see
Figure 3-35.
Table 3-39. HART/BTI Switch Settings for SW3 and SW4 (for Non multi-dropped HART devices only)
Switch Number Setting ( BOLD =Factory default)
IN=position away from the dot on the switch
SW3
IN Channel 1 is an analog input.
OUT Channel 1 is an analog output.
SW4
IN Channel 2 is an analog input.
OUT Channel 2 is an analog output.
Setting Jumpers
To locate jumpers, see Figure 3-35.