Instruction manual
ControlWave Micro Instruction Manual (CI-ControlWave Micro)
Revised Jun-2013 I/O Modules 3-55
Detailed Technical
Specifications
For detailed technical specifications, please see our website
http://www.emersonprocess.com/remote.
Configuration
The non-isolated HART/BTI module (general part number 396983-
XX-X) has the following configurations:
Table 3-36. Non-Isolated HART/BTI Interface Module
Part Number Termination Connector Notes
396983-01-4
local
396983-02-2
remote
Wiring the Module
The HART/BTI module includes eight 4-20 mA input channels, two of
which you can optionally re-configure as 4-20 mA output channels. All
eight channels are individually selectable for either HART, Bristol
transmitter, or 4-20 mA analog input operation. The first four channels
are on the main board; the second four channels are on the daughter
board.
You connect the module and the device (either HART, 3508, or 3808)
using two-wire current-sourced twisted pair copper wire.
Refer to the figures and tables that follow for wiring configurations to
the board.
Figure 3-31. TB1 and TB2 Terminal Blocks
Table 3-37. HART/BTI Wiring Connections – Local Termination
TB1 Wiring Connections TB2 Wiring Connections
1 CHANNEL 1 1 CHANNEL 5
2 ISOGND 2 ISOGND
3 CHANNEL 2 3 CHANNEL 6
4 ISOGND 4 ISOGND
5 CHANNEL 3 5 CHANNEL 7
6 ISOGND 6 ISOGND
7 CHANNEL 4 7 CHANNEL 8
8 ISOGND 8 ISOGND