Instruction manual
ControlWave Micro Instruction Manual (CI-ControlWave Micro)
3-52 I/O Modules Revised Jun-2013
Thermocouple
Type
Process Temperature
Range
RTD Error with CJC
@ 25C
E
– 270C to – 261C
– 260C to – 245C
– 244C to – 200C
– 200C to – 87C
– 86C to +25C
+25C to 100C
10C
3C
1.50C
0.75C
0.39C
0.30C
K
– 270C to – 261C
– 260C to – 247C
– 246C to – 222C
– 220C to – 160C
– 159C to +25C
+25C to 1372C
15.00C
4.50C
2.20C
1.10C
0.55C
0.30C
T
– 270C to – 261C
– 260C to – 243C
– 242C to – 196C
– 195C to – 61C
– 60C to +25C
+25C to 400C
10.30C
3.00C
1.50C
0.75C
0.375C
0.30C
Note: Use straight-line approximation to calculate approximate error between
end points.
Software Configuration
To use data from an Isolated Low Level Analog Input module you
must add a CWM_TC6 board in ControlWave Designer’s I/O
Configurator, and then configure it. See the ControlWave Designer
Programmer's Handbook (D5125) for more information. That same
manual includes an I/O Mapping section that describes, for advanced
users, the I/O map for this module.