Instruction manual
ControlWave Micro Instruction Manual (CI-ControlWave Micro)
3-48 I/O Modules Revised Jun-2013
3.15 Isolated Low Level Analog Input (LLAI) Module
Low Level Analog Input (LLAI) modules provide six individually
isolated differential inputs for thermocouples or 10mV inputs plus one
cold junction compensation (CJC) input for temperature compensation
at the terminal block.
Table 3-32. Isolated LLAI Module Characteristics
Type Number
Supported
Characteristics
Isolated Low
Level Analog
Input (LLAI)
6
Each isolated LLAI supports/includes:
Signal conditioning circuitry including a
2.5V reference
Surge suppression with a 188V
Transorb that meets IEEE standard
472-1978.
Over voltage protection
Opto-isolation circuitry.
Each input is
provided electrical isolation of 500Vdc
(channel to channel/system bus).
24-bit analog to digital converter (ADC)
The CJC with a built-in RTD provides thermocouple temperature
compensation at the terminal block and is electrically isolated. Pins 8, 9
and 10 of the local terminal block (TB1) source and sink the CJC’s
RTD.
Detailed Technical
Specifications
For detailed technical specifications, please see our website
http://www.emersonprocess.com/remote.
Configuration
The isolated LLAI module (general part number 396875-XX-X) has
the following configurations:
Table 3-33. Isolated LLAI Module Configurations
Part Number Termination Connector Notes
396875-01-7
local
396875-02-5
remote
Wiring the Module
Figure 3-29 shows field wiring for locally terminated isolated LLAI
modules. Figure 3-30 shows field wiring for remotely terminated
isolated LLAI modules.
Figure 3-29 also provides diagrams showing the wiring for
thermocouples and the 3-wire cold junction compensation (CJC) PCB to
a locally terminated LLAI module (that is, +AI#, -AI#, +CJC
(Reference), -CJC (Return) & +CJC (Sense) are similar to those
assigned to the remote DIN-rail mountable terminal blocks. A small
CJC PCB is factory-installed to the terminal block.