Product data

June 2012
CWGFC
10 www.EmersonProcess.com/Remote
Maximum load
current
400 mA at 16 V and 400 mA at 30 V
Maximum update
rate
Once per 250 ms
Electrical isolation None
Surge Suppression
meets ANSI/IEEE C37.90-1978; 30 V transorb between signal and
ground
Terminations Pluggable terminal block accommodates up to 16 gauge wire size
High Speed Counter/Discrete
Inputs 5,6
Type 2, also operable as DI points
Type Dry contact
Frequency range 0 to 10,000 Hz or 0 — 30 Hz; switch selectable
Input Range Internally sourced dry contact input
Input filtering 20 μs or 1 ms; switch selectable
Accumulator 16 bit
Maximum scan
rate (program
scan of the
accumulator)
Once per 250 ms
Input current 200 μA per input at 3.3 V
On State <1.21 V
Off State >2.07 V
Surge suppression
MeetsANSI/IEEEC37.90‐1978;30Vtransorbbetweensignaland
ground
Terminations
Pluggableterminalblockaccommodatesupto16gaugewiresize
Analog Inputs (optional) Quantity 3
Resolution 14 bit
Input
configuration
Externally sourced single-ended inputs, jumper selectable 4 to 20 mA
or 1 to 5 Vdc
Input impedance 1 MΩ, 4 to 20 mA
Input filtering 12 Hz
Maximum scan
rate
Once per 250 ms
Channel settling
time
600 ms to be within 0.01% of input signal
Input accuracy 0.1% of span at 25ºC
0.2% of span -40 to 70ºC
Surge
Suppression
Meets ANSI/IEEE C37.90-1978; 30 V transorb between signal and
ground
Terminations Pluggable terminal block accommodates up to 16 gauge wire size