Product data

Product Data Document
1660ds9b / D301294X012
October 2011 - Page 8
ControlWave GFC Plus
Remote Automation Solutions
www.EmersonProcess.com/Remote
Average Specic Gravity
Average Heating Value
Flow Time
Uncorrected Count
Each log entry also contains the date and time.
ControlWave GFC Plus has an Hourly Historical Log
for each run.
Daily Historical Data Log
The Daily Data Log holds one record for every
contract day. The contract hour may be changed
by the user. The daily log holds 62 entries; this
ensures that the previous calendar month of daily
data is always resident in ControlWave GFC FLASH
memory. The following items are stored in the Daily
Data Log:
Corrected Volume
Uncorrected Volume
Accumulated Energy
Average Static Pressure
Average Temperature
Average Differential Pressure
Average Specic Gravity
Average Heating Value
Flow Time
Uncorrected Count
Each log entry also contains the date and time.
ControlWave GFC Plus has a Daily Historical Log
for each run.
Periodic Historical Data Log
The periodic data log holds one record for every log
interval. Log interval is 15 minutes. The Periodic
Historical Data Log holds 1440 records, or four days
of 15 minute data. The following items are stored in
the Periodic Historical Data Log:
Flowing Differential Pressure
Flowing Static Pressure
Flowing Temperature
Frequency
Each log entry also contains the date and time.
ControlWave GFC Plus has a Periodic Historical
Data Log for each run.
Audit Trail Alarm and Event Storage
ControlWave GFC keeps an Audit Trail Buffer ca-
pable of storing the most recent 500 Alarms and the
most recent 500 Events. Internally, these buffers are
maintained separately to prevent recurring alarms
from overwriting conguration audit data. Externally,
they are reported to the user as a single entity. Both
operate in a circular fashion with new entries over-
writing the oldest entry when the buffer is full. The
following circumstances cause an entry to be made
in the Audit Trail Buffer:
Any operator change to a ControlWave GFC
Plus conguration variable
Any change in the state of a ControlWave GFC
Plus alarm signal
A system restart
Certain other system events
Includes a nominations function
Allows the user to select engineering units from
a broad variety, including English and metric
Interfaces to a chromatograph and provides
energy throughput as well as composition
information (note that the same port is
allocated for either a chromatograph or external
transmitters).
Self Diagnostics
ControlWave GFC Plus periodically runs a series of
diagnostics to verify the operational status of vari-
ous system components. The tests include trans-
ducer parameters, main and backup battery volt-
ages, software sanity checks, and other indications
of system health. An appropriate alarm is generated
if any test fails.