Specications–OperatingEnvironment
Wide operating power input voltage range of 5.0 •
to 18.0 Vdc
While this product can operate with nominal •
power inputs as low as 6 Vdc, note that 12 Vdc
nominal is required if an internal radio is used.
Operating Temperature Range: -40 to 158ºF •
(-40 to 70ºC)
Operating Temperature Range of Lead Acid Cell •
Batteries is more restrictive: -4 to 140ºF (-20 to
60ºC)
Operating Humidity Range: 10 to 95% RH non-•
condensing
Vibration Rating: Maintains proper operation •
while subjected to a 2.0g acceleration over 10-
150 Hz and 1.0g acceleration over 150-2000 Hz
(ISA Process Mount)
Electrostatic Discharge: Meets IEC EN 61000-•
4-2, EN 61326
RFI Immunity: In conformity with ENV 50140 •
radio-frequency electromagnetic eld amplitude
modulated EMC
EMC Emissions: EN 55022:1998 Class A •
ITE emissions requirements (EU); ICES-003
Issue 3 Class A Digital Apparatus emissions
requirements (Canada); AS/NZS3548:1995/
CISPR Class A ITE emissions requirements
(Australia)
Nema Rating: Nema 3R (Nema 4x except with a •
battery vent)
Hazardous Area Approvals
UL approved as non-incendive for operation •
in Class I, Division 2 hazardous areas for all
congurations
Performance
Computation Accuracy: 0.01% Corrected Flow, •
including all input values
DP Reference accuracy: 0.075% URL•
Static Pressure Reference Accuracy: •
0.035% URL
Pressure Effect on DP: 0.1% URL zero and •
0.1% URL span
Temperature Effects: 0.21% URL•
SELECTION ITEM DESCRIPTIONS AND
SPECIFICATIONS
ControlWave GFC Plus is ordered using a model
number specication. The complete model number
specication is included at the end of this product
data document.
Standard equipment includes berglass housing
with 2-line LCD and 2 function keys, ControlWave
Express RTU package with single board main elec-
tronics assembly and the standard API 21.1 ow
measurement application program. Standard I/O
count is 2 DI/PI (Pulse Inputs).
Also included in the base product are interfaces to
Emerson’s gauge pressure or multivariable, DP/P
sensor assembly, an RTD interface, and an AUX
power output (e.g. to switch power to a radio).
The model number additionally allows a user to
specify all of the following:
Integral, gauge pressure or multivariable (MVT), •
DP/P sensor assembly and upper range limits.
Bendable RTD assembly, pre-wired•
Thermowell•
A two-line LCD with two pushbuttons or a four-•
line LCD with 25-key keypad
I/O card, including 2 DI/DO, 4 DI, 2 DO and 2 •
HSC/DI and, optionally, an additional 3 AI, 1 AO
Hazardous area approval – Class I, Division 2•
Choice of integral, battery and solar power •
systems
Choice of standard model modem or radio that •
is installed on an internal bracket. Standard
radios are those that are commonly available
from Freewave and MDS.
Polyphaser surge suppressor for the radio•