Product data

Product Data Document
1660ds9b / D301294X012
October 2011 - Page 3
ControlWave GFC Plus
Remote Automation Solutions
www.EmersonProcess.com/Remote
www.ControlWave.com
Specications–OperatingEnvironment
Wide operating power input voltage range of 5.0
to 18.0 Vdc
While this product can operate with nominal
power inputs as low as 6 Vdc, note that 12 Vdc
nominal is required if an internal radio is used.
Operating Temperature Range: -40 to 158ºF
(-40 to 70ºC)
Operating Temperature Range of Lead Acid Cell
Batteries is more restrictive: -4 to 140ºF (-20 to
60ºC)
Operating Humidity Range: 10 to 95% RH non-
condensing
Vibration Rating: Maintains proper operation
while subjected to a 2.0g acceleration over 10-
150 Hz and 1.0g acceleration over 150-2000 Hz
(ISA Process Mount)
Electrostatic Discharge: Meets IEC EN 61000-
4-2, EN 61326
RFI Immunity: In conformity with ENV 50140
radio-frequency electromagnetic eld amplitude
modulated EMC
EMC Emissions: EN 55022:1998 Class A
ITE emissions requirements (EU); ICES-003
Issue 3 Class A Digital Apparatus emissions
requirements (Canada); AS/NZS3548:1995/
CISPR Class A ITE emissions requirements
(Australia)
Nema Rating: Nema 3R (Nema 4x except with a
battery vent)
Hazardous Area Approvals
UL approved as non-incendive for operation
in Class I, Division 2 hazardous areas for all
congurations
Performance
Computation Accuracy: 0.01% Corrected Flow,
including all input values
DP Reference accuracy: 0.075% URL
Static Pressure Reference Accuracy:
0.035% URL
Pressure Effect on DP: 0.1% URL zero and
0.1% URL span
Temperature Effects: 0.21% URL
SELECTION ITEM DESCRIPTIONS AND
SPECIFICATIONS
ControlWave GFC Plus is ordered using a model
number specication. The complete model number
specication is included at the end of this product
data document.
Standard equipment includes berglass housing
with 2-line LCD and 2 function keys, ControlWave
Express RTU package with single board main elec-
tronics assembly and the standard API 21.1 ow
measurement application program. Standard I/O
count is 2 DI/PI (Pulse Inputs).
Also included in the base product are interfaces to
Emerson’s gauge pressure or multivariable, DP/P
sensor assembly, an RTD interface, and an AUX
power output (e.g. to switch power to a radio).
The model number additionally allows a user to
specify all of the following:
Integral, gauge pressure or multivariable (MVT),
DP/P sensor assembly and upper range limits.
Bendable RTD assembly, pre-wired
Thermowell
A two-line LCD with two pushbuttons or a four-
line LCD with 25-key keypad
I/O card, including 2 DI/DO, 4 DI, 2 DO and 2
HSC/DI and, optionally, an additional 3 AI, 1 AO
Hazardous area approval – Class I, Division 2
Choice of integral, battery and solar power
systems
Choice of standard model modem or radio that
is installed on an internal bracket. Standard
radios are those that are commonly available
from Freewave and MDS.
Polyphaser surge suppressor for the radio