Revised Feb-2013 Service & Troubleshooting 5-5
xxxxx varies from release to release) and click Send to start the
flash upgrade (see Figure 5-4). When you see the
HyperTerminal Mode Menu again, it means the download has
completed.
9. Exit HyperTerminal and power down the ControlWave GFC
Plus. If desired, you can disconnect the null modem cable
between the ControlWave GFC Plus and the PC.
10. Set switch SW1-3 to the OFF position (OFF = Recovery Mode
Disabled).
11. Restore power to the ControlWave GFC Plus.
Figure 5-3. Send File dialog box
E1S0410.bin
CWEXP01
Figure 5-4. HyperTerminal (Download in Progress)