Instruction manual
ControlWave Gas Flow Computer (GFC Plus) Instruction Manual (CI-ControlWave GFC Plus)
2-28 Installation Revised Feb-2013
Table 2-7. RS-232 COM1 and COM2 Port Connector Pin Assignment
Pin
RS-232
Signal
RS-232 Description
Local Port Pin# Local Port Notes:
1 DCD Data Carrier Detect Input 1 (Green wire)
2 RXD Receive Data Input 2 (Red wire)
3 TXD Transmit Data Output 7 (White wire)
4 DTR Data Terminal Ready Output 4 (Brown wire) Pin 4 connected to pin 4 at
TB5 of CPU = external power
for local communication port
cable.
5 GND Power Ground 6 (Black wire)
6 DSR Data Set Ready Input
7 RTS Request to Send Output
RTS connected to CTS at J4
of CPU for local port
communication cable.
8 CTS Clear to Send Input
RTS connected to CTS at J4
of CPU for local port
communication cable.
9 N/A
Use the “null modem” cable for full-duplex (PPP protocol)
communications when connecting a ControlWave GFC Plus to a PC.
(See top part of Figure 2-17.)
Table 2-8. RS-232 COM1 (J11) Alternate Connector Pin Assignment
Pin
RS-232
Signal
RS-232 Description
1 GND Power ground
2 RXD Receive data input
3 TXD Transmit data output