Instruction manual

ControlWave Gas Flow Computer (GFC Plus) Instruction Manual (CI-ControlWave GFC Plus)
2-14 Installation Revised Feb-2013
2.3 Configuring the CPU/System Controller Board
The CPU/System Controller board is situated on the right side of the
Process I/O board; the combined assembly mounts vertically on edge on
the inner left side of the enclosure. To configure the CPU/System
Controller board, you need to set some switches and jumpers.
1
2
3
4
5
6
Power In +
Aux. Power Out +
Solar Pwr. In +
GND
GND
GND
1
2
3
4
5
6
7
8
TXD
GND
DCD
RXD
DTR
DSR
RTS
CTS
1
2
3
4
5
6
7
8
TXD
GND
DCD
RXD
Input
Input
Output
Output
Output
Input
Input
Input
Input
Output
Output
Output
Input
Input
DTR
DSR
RTS
CTS
1
2
3
4
5
TXD-/TXD
GND
RXD+
RXD-/RXD
Input
Input
Output
Output
TXD+
4
1
2
3
GND
PULSE 1
PULSE 2
Input
Input
1
2
3
RTD-
RTD EXC
RTD+
Output
PULSE
PWR
COM1
S1
1
2
3
4
12
3
45678
RJ-45
W3 - 1-2 = Battery Enabled
2-3 = Battery Disabled
W2 - 1-2 = COM2 CTS from Port
W5 - 1-2 = 12/24V Power Supply
Shut-down Hysterisis
Shut-down Hysterisis
2-3 = 6V Power Supply
W6 - 1-2 = 12V Power Supply
Shut-down
Shut-down
2-3 = 6/24V Power Supply
2-3 = COM2 CTS to RTS
W1 - 1-2 = COM1 CTS from Port
2-3 = COM1 CTS to RTS
W7 - 1-2 = 12/24V Power Fail
Trip Point Hysterisis
Trip Point Hysterisis
2-3 = 6V Power Fail
W8 - 1-2 = 12V Power Fail
Trip Point
Trip Point
2-3 = 6/24V Power Fail
SW3 - COM3 Config.
RS-485 Receiver Biasing & Termination
2-Wire, 4-Wire Selection
J5 - COM3
Piggy-back
Radio Intf.
J3 - I/OBUS
Intf. to
CPU Board
P1
WE
J7
MSP430
JTAG
Header
J9
PLD JTAG
Header
J8
Emulation
Header
J3
J5
W14
W16
W7
W1
W2
W3
W8
W6
W5
W15
W12
W13
COM2
RS-232
COM3
RS-232
RS-485
Radio
Pulse
Input
LCD/
Keypad
Power
1
5
6
9
Configuration
Options
Switch
Recovery
Mode &
COM./Status
LEDs
1
O
N
2
3
4
O
N
1
2
3
4
5
6
7
8
RTD
Input
CR1
Watchdog
Idle
W17 - 1-2 = 6V Input Power
2-3 = 12V Input Power
W12 - W16 - 1-2 = COM3 RS-232
2-3 = COM3 RS-485
NOTE:
J7, J8, J9
Factory Use
W17
Fuse:
F3 on
Non Intrinsically
Safe Units
F3
1
2
GND
Sec. Battery Input
Power
RJ-45
10/100
Base-T
Ethernet
Port
Receive
LED
RJ-45
Transmit
LED
3 2 1
T
X
D
R
X
D
G
N
D
COM1
RS-232
NOTE:
J11 normally used
for CW GFC and CW
Express PAC only.
W18
W18: COM1 connector
selection
1 to 2 = J4 active
2 to 3 = J11 active
Damage WILL occur to
the CPU if the Ethernet
network is connected
to connector J2!
CAUTION:
Solar Pwr. In and Aux. Power Out
are not available on units equipped
with an Ethernet Port.
Ultra Low Power CPU/System
Controller Bds. don’t have an
Ethernet Port.
NOTE:
Do Not Connect a 24V Solar Panel
to Connector TB1-1 & TB1-2!
Figure 2-8. - CPU/System Controller Board Component I.D. Diagram
NOTE: Carefully
examine DIP
switches to verify
proper ON/OFF
position. Different
versions of the
board may have
different switch
positions.