Specifications
Supplement – CW-GFC-IS
COM2 and COM3 wiring connections are located on terminal block
TB3 (See Figure 2). Wiring for these ports routes out of the unit through
the conduit to the ISTRAN. See CI-CW-GFC-ISTRAN for details on the
interface.
Note: Consult the diagram on the next page for terminal connections.
Wiring the Power Connections
You must connect power using both the solar panel connector (TB1) on
the termination panel and the battery 1 connector (TB2). You can
connect TB2 to an intrinsically safe communication interface (ISTRAN)
or an internal 6V 7AH lead acid battery. DO NOT USE the battery 2
connector (P6).
Warning
Only use battery and solar panels shipped from the factory with the unit
according to the model specification. Using batteries or solar panels
from third parties violates the intrinsically safe certification for the
system.
Figure 6. Power Connectors for Solar Panel and Battery 1
Note: Consult the wiring diagram on the next page for terminal
connections.
Issued Nov-09 Supplement to CI-ControlWave GFC / CI-ControlWave Corrector 5