User manual
6 • CH Breaker Gateway I&O Manual 026-1710 Rev 1 05-15-07
5.2.2. Adding Lighting Schedule Appli-
cations
For each group of breakers to be controlled separately,
set up a Lighting Schedule application from the Add New
Application screen.
1.
Add/Delete Application
2.
Add New Application
3. DLOOK UP to select Lighting Control.
Enter the number of desired applications in
the How Many? field.
If using an Einstein controller, from the Home screen or
Enhanced Lighting Status screen, press
((Actions),
(Control Appl Setup), and then (Add Control Ap-
plication). Press
'(Look Up) to select Enhanced
Lighting. Press
)(Home) to return to the Home screen.
5.2.3. Proof Inputs and Light Outputs
Setup
Once the Lighting Schedule applications have been
added, set up the proof inputs and light outputs for each
Lighting application. The outputs of a Lighting Schedule
cell control the breakers on the Cutler-Hammer panels, and
the inputs are the combined proofs of all the breakers that
are part of the group being controlled by the application.
5.2.3.1. Proof Inputs Setup
Set up 16AI board inputs in Proof Setup. To enable
proofing, set Enable Proofing to Yes for each Light-
ing application by accessing the Lighting Control Setup
screen. From the Main Menu:
1. Press C(Lighting Sched) and select the a
Lighting application.
2. E(Setup) to go the Setup screen for that
Lighting application.
If using an Einstein controller, from the Home screen
or Enhanced Lighting Status screen, press
((Actions),
(Setup), and choose the S1:Setup tab. (Note that the
Proof tab is S8 and the Outputs tab is S9).
3. Under the C1:Setup tab, set Enable
Proofing to Yes. (C8:Proof tab be-
comes visible once you cursor across the tabs.
See Figure 5-3.)
4. Press B(Next Tab) or A(Prev Tab) to
cursor over to C8:Proof tab.
TRY THIS: When creating a name for your
Lighting application, incorporate the applica-
tion’s corresponding group number into the
name. For example, PARKLIGHTS01 associates the
parking lot breakers with Group 1.
Figure 5-2 - Setup Lighting Control