Specifications

9-8E2 RX/BX/CX I&O Manual 026-1610 Rev 10 06-APR-2010
Board/Point # The Board/Point number will auto-
matically be defined if you are configuring the point
from the Input Status screen, and indicates the physi-
cal address of the board.
Point Name The Point Name is simply a name for
the point that may be used as a reference.
Assigning a descriptive name to a point makes set-
ting up inputs for applications much easier. For
example, if you have an inside temperature sensor
located in Zone 1 of your building, you may name it
“ZONE 1 TEMP”. Then, when programming your
HVAC applications, you may easily define Zone 1’s
temperature sensor input by tying it to ZONE 1
TEMP. This keeps you from having to keep track of
which sensors are tied to which point numbers.
You are required to enter a point name in the Point
Name field. The default name is “:{BOARD
NAME}:{UNIT NUMBER}:{BOARD NUM-
BER}:{POINT NUMBER}.”
Sensor Type The analog input may come from a
number of different sensor types.
Figure 9-6
- Analog Input Screen
Sensor Type Description
Temperature Retail Solutions Standard
Temp Sensor
5V-100 PSI 5VDC 100 PSI transducer
(0.5-4.5VDC output)
5V-200 PSI 5VDC 200 PSI transducer
(0.5-4.5VDC output)
5V-500 PSI 5VDC 500 PSI transducer
(0.5-4.5VDC output)
12V-100 PSI 12VDC 100 PSI transducer
(1-6VDC output) (Discontin-
ued)
12V-200 PSI 12VDC 200 PSI transducer
(1-6VDC output) (Discontin-
ued)
12V-500 PSI 12VDC 500 PSI transducer
(1-6VDC output) (Discontin-
ued)
Refrig. Leak Refrigerant Leak Detector
(not IRLDS)
Refrig. Level Refrigerant Liquid Level
Probe
Liquid Level Liquid Level Float Sensor
Light Level Light Level Sensor
Linear General purpose linear out-
put sensor
Humidity Relative Humidity sensor
Pulse Accum. Kilowatt value from KW
transducer pulse accumula-
tion readings (see Units Per
Pulse on
page 9-9)
KW Transducer Kilowatt transducer using 4-
20ma/0-5V signal
Dewpoint Dewpoint probe
LM235 Temp Linear voltage output tem-
perature sensor
PT2 Temp Danfoss PT2 temperature
sensor
CDK Temp CDK 2097MC temperature
sensor
Table 9-2 - Sensor Input Types