Specifications

10-26E2 RX/BX/CX I&O Manual 026-1610 Rev 10 06-APR-2010
1. Press the key to open the Main Menu
screen.
2. Select
(Add/Delete Application) to open the
Add/Delete Application menu.
3. Select
to add an application.
4. Choose an application by pressing (LOOK
UP) to open the Option List Selection menu, and
choose the application you wish to add.
5. Press
to place the application in the Type
field.
6. Select the number of applications you wish to add
in the How many? field.
7. Press
to add.
8. You are then asked if you would like to edit the
application now. Press Y (Yes) or N (No).
Delete an Application
:
1. Press the key to open the Main Menu
screen.
2. Select
(Add/Delete Application) to open the
Add/Delete Application menu.
3. Select
(Delete Application).
4. Press
to delete the application if not dis-
played by default.
5. If not displayed by default, choose the applica-
tion you wish to delete by selecting (LOOK
UP). The Option List Selection menu opens.
Choose the application you wish to delete from
this list.
6. Press
and the application appears in the
Type field.
7. Press
to delete the application.
8. A dialog box opens asking if you are sure you
want to delete the application you have selected.
Press Y (Yes) or N (No).
10.18.2 Using and Configuring a
Setup Screen
The Setup screen is application-specific depending on
where you place the cursor on the Home screen.
Press
to open the Actions Menu and select
(Setup), or press (SETUP) on the Home screen.
The Setup screen for your selected application will
open.
10.18.2.1 The Edit Menu
The Edit menu becomes available when you are on a
Setup screen and can be opened by pressing (EDIT).
Depending on which Setup option (index tabs) is high-
lighted, the Edit menu allows you to change field format-
ting using these options:
Alternate I/O Formats - setting up pointers can
change a field to expect a Board:Point, Fixed
Value, or Area Ctrl:Application:Property.
Set Multiple Outputs - allows you to connect an
output pointer to multiple input pointers.
Output Change Delta - the +/- change that must
occur at the output before the new value is used.
Generic Alarm Setup - enables the user to custom-
assign alarming parameters in the controller.
Logging Setup - enables the user to turn logging on
for a particular parameter. Note that if “L” appears
next to the parameter, default logging has already
been enabled for the Logging Group Cell.
Bypass Setup - Opens screen for bypass input
types, which are “Momentary” or “Level” triggered
and remain active for a “Bypass Duration”. For
example, Time Schedules have two such inputs.
I/O Mode - toggles between displaying board
names and board numbers.
Setup I/O - allows user to enter an input or output
point setup screen.
10.18.2.2 Entering Setpoints
An application setpoint is a user-defined control
Figure 10-46
- Edit Menu