Specifications

9-18E2 RX/BX/CX I&O Manual 026-1610 Rev 10 06-APR-2010
9.4 CCB Case Controllers
For information on retrofitting E2s in RMCC stores
with CCBs, refer to Technical Bulletin #026-4119. For
other information about CCB wiring, hand-held terminal
programming and operation, refer to the CCB Installation
Manual (P/N 026-1110).
9.5 ESR8 and MultiFlex
ESR Valve Output Wiring
ESR8 Boards (Discontinued)
For ESR8 boards, the stepper valves are wired to the
board by connecting the four-conductor wire from the
stepper valve to a connector plug and then plugging in to
one of eight jacks along the top of the board
Figure 9-19.
Use the cable harnesses supplied with the valves or use
Belden #9418 four-conductor 18AWG wire.
If the stepper valves have block-style connectors, cut
the ends off and attach the terminal plugs supplied with the
ESR8 to the wire ends.
MultiFlex ESR Board
The stepper valves are wired to the board by connect-
ing the stepper valve harness to one of the eight screw ter-
minal connectors along the top of the board (Figure 9-20)
and matching the wire colors to the legend on the connec-
tors. Use the cable and cable harnesses that are supplied
with the valves.
Wire on Valve
Cable 335-3260
Emerson
Flow Con-
trols ESR
Emerson
Flow Con-
trols ESV
Sporlan
SEI&CDS
Pin # Color
1 Red Red Blue Red
2 Black Blue Red Green
3 Blue Black Black Black
4 Green White White White
5 White Yellow
6 Brown
Table 9-5
- 335-3260 to Valve Connection Information
NOTE: A wire run may not be longer than 150
ft. using Belden #9418.
Figure 9-19 - ESR8 Valve Wiring
NOTE: For Sporlan CDS, wire the same as
Emerson Flow Controls ESR, but use green
wire in place of blue wire.
Figure 9-20
- ECT Flow Valve and MFlex ESR Board Wiring
WHITE
BLACK
BLUE
RED
S
T
E
P
P
E
R
V
A
L
V
E
TOP OF BOARD
Pin 1
Emerson
Flow
Controls ESR
ECT Flow
Stepper Valve
MultiFlex ESR Board w/ Eight
Screw Terminal Connectors
(P/N 810-3199)
Stepper Valve
Harness
WHITE
BLACK
RED
BLUE
Match wire colors to
silk screen legend on
board terminals