Setup guide
Setting up the Host to Reference the I/O Rack
30
These variables are:
Variable Description
ERSTAT_x_BOARDSTATUS Board status code. Always present.
ERSTAT_x_BATSTAT Battery status. Always present.
ERSTAT_x_HOTCARDSTAT Hot Card Replacement in progress. Always present.
ERSTAT_x_HOTCARDCT Count of number of hot card replacement operations
ERSTAT_x_DOWNTIMEUSER User configured down time for I/O Expansion Rack
ERSTAT_x_DOWNTIMEACT Actual time rack was down
ERSTAT_x_WRITECT Number of writes to rack
ERSTAT_x_READCT Number of reads (updates sent from rack)
ERSTAT_x_CONNECTS Number of IP connections or re-connects to rack
ERSTAT_x_HEARTBEAT Heartbeat count
ERSTAT_x_MASTER_IS_B This is used in Redundant I/O Racks. This value is set
TRUE when the “B” unit is the primary online (master)
unit.
ERSTAT_x_STBYVALID This is used in Redundant I/O Racks. This value is set
TRUE when the standby (backup) unit is ready to take over
in the event of a failure of the primary online unit (master).
ERSTAT_x_FAILOVERERR This is used in Redundant I/O Racks. This is set TRUE if
an error occurs during an attempted forced failover from
the online unit to the backup unit.
ERSTAT_x_REDUNSTAT This is used in Redundant I/O Racks. This is a status code
related to redundant operations.
ERSTAT_x_FAILOVER_O This is used in Redundant I/O Racks. It may be set TRUE
by the user’s application to force a failover between the
online rack and the backup rack. After the failover occurs,
it will automatically be set FALSE. If it is set TRUE, and
remains TRUE, that means a forced failover was not
possible.
ERSTAT_x_BDSTR1 to
ERSTAT_x_BDSTR8
ID strings for I/O cards in the rack.