Setup guide
Setting Configuration Parameters
19
Redundancy Transfer
Unit A Addr
This must be an IP address corresponding to an Ethernet port on the
‘A’ I/O Expansion Rack in a redundant pair.
Unit B Addr
This must be an IP address corresponding to an Ethernet port on the
‘B’ I/O Expansion Rack in a redundant pair.
MODBUS Write Access
Serial Failover
Enabled
Normally, should communications be lost between the host
ControlWave and the I/O Expansion Rack, the I/O points are set to the
‘safe’ state described under “Host Comm Loss Timeout”. When
“Serial Failover Enabled” is checked, however, write control through
serial MODBUS communications are allowed with the I/O Expansion
Rack, even though communications with the host ControlWave have
been lost. This allows control operations to continue via the I/O rack,
until Ethernet communication with the host can be re-established.
This is also true in cases where a redundant pair of I/O Expansion
Racks have been configured; a failover from the on-line rack to the
standby rack will not occur just based on a loss of communications
with the host, if serial MODBUS communications are still active.
In order for the “Serial Failover Enabled” feature to work, MODBUS
communications must have been fully pre-configured, and ready to use
when communications are lost with the host. If serial MODBUS
communications fail, and the user configured “Host Comm Loss
Timeout” has expired, all outputs will be set according to the “Host
Comm Loss Timeout” description, above.
NOTE: Serial MODBUS read requests are unaffected by the “Serial
Failover Enabled” check box. Reads are always allowed. Serial
MODBUS writes are only allowed when “Serial Failover Enabled” is
checked.
The “Serial Failover Enabled” feature requires firmware 04.00 or
newer.