Instruction manual
CI-ControlWaveLP Specifications / 4-9
Status Indication: 8 LEDs (one per point) (CR49 - CR56)
Bus Access: 16 Bits Wide
Maximum Load: 100mAdc @ 35Vdc
4.3.4 High Speed Counter
Number of Inputs: 4
Input Voltage Range: 12V or 24V
Input Frequency: 10KHz Max.
Input filtering: 20 microseconds
Input configuration: Set/Reset inputs, contact closure, externally sourced on
point by point basis with jumper configuration.
Input current: 2.5mA ± 10%
‘1’ State Voltage: 90% of input voltage range
‘0’ state voltage: 10% of input voltage range
Bus Access: Sixteen bits wide
Max. Accumulator Value: 65536
Electrical isolation: 1500Vdc
Surge Suppression: 500Vdc MOV to CHASSIS
38Vdc MOV across input and to FIELD COMMOM
Meets ANSI/IEEE C37.90-1978
Terminations: Pluggable, (TB4) max wire size is 16 gauge
Status Indication: LED per point (DS95 - DS98)
4.4 ENVIRONMENTAL SPECIFICATIONS
Temperature: Operating: -40 to +158 °F (-40 to +70 °C)
Storage: -40 to +158 °F (-40 to +70 °C)
Relative Humidity: 0-95% Non-condensing
Vibration: 1g for 10 - 150 Hz
.5g for 150 - 2000 Hz
Shock: 30g (11 msec duration)
50g (11 msec duration)