Instruction manual
4-8 / Specifications CI-ControlWaveLP
4.3.2 Discrete Inputs
Number of Inputs: 16
Input Voltage Range: 12V or 24V
Input Filtering: 1 millisecond or 30 milliseconds
Input Configuration: Contact Closure, externally sourced on a point by point
basis - Jumper configurable
Input Current: 2.5mA ±10%
‘1’ State Voltage: 90% of input voltage range
‘0’ State Voltage: 10% of input voltage range
Interrupt generation: On change of state transition on a point by point basis
Bus Access: Sixteen Bits Wide
Electrical Isolation: 1500Vdc
Surge Suppression: 500Vdc MOV to CHASSIS
38Vdc MOV across input and to FIELD COMMON
Meets ANSI/IEEE C37.90-1978
Terminations: Pluggable (TB1), maximum wire size is 16 gauge
Status Indication: 16 LEDs (one per point) (CR33 - CR48)
Input Type: Isolated Voltage Input
Isolated Current Input
Transmitter Current Loop
4.3.3 Discrete Outputs
Number of Outputs: 8
Output Type: Open Drain
Surge Suppression: 500Vdc MOV to CHASSIS
38Vdc MOV Across Output
Meets ANSI/IEEE C37.90-1978
Max. Operating Voltage: 38Vdc
Max. Operating Frequency: 20 Hz
Current Sink: 100mA Maximum
Electrical Isolation: 1500Vdc
Terminations: Pluggable (TB2), maximum wire size is 16 gauge