Instruction manual

CI-ControlWaveLP Service / 3-7
Table 3-1 - FMI/OB Board LED Assignment (Continued)
Name Function
On
Operation
Name Function
On
Operation
CR40 DI8 Data High CR111 IDLE System Halted
CR41 DI16 Data High CR112 WDOG Watchdog Occured
CR42 DI9 Data High CR113 STATUS 1 Firmware Defined
CR43 DI10 Data High CR114 STATUS 2 Firmware Defined
CR44 DI11 Data High CR115 STATUS 3 Firmware Defined
CR45 DI12 Data High CR116 STATUS 4 Firmware Defined
CR46 DI13 Data High CR117 STATUS 5 Firmware Defined
CR47 DI14 Data High CR118 COM2_RX/COM2_TX TX/RX Data High
CR48 DI15 Data High CR120 COM3_RX/COM3_TX TX/RX Data High
CR49 DO8 Data High CR121 COM4_RX/COM4_TX TX/RX Data High
CR50 DO1 Data High CR122 COM5_RX/COM5_TX TX/RX Data High
CR51 DO2 Data High CR134 MCLED* MC* Inactive
CR52 DO3 Data High CR135 FPINLED* PFIN* Inactive
CR53 DO7 Data High CR136 COM1_RX/COM1_TX TX/RX Data High
CR54 DO6 Data High - -
Figure 3-6 - Discrete Input (DI) LED Assignments