Instruction manual
2-34 / Installation CI-ControlWaveLP
Figure 2-34 - HyperTerminal FLASH Download (Download in Process)
Table 2-15 - PORT 80 - Running Status Codes
Status LEDs
1 2 3 4 5 6
Definition Notes
0 0 0 0 0 0 No application
0 0 0 0 0 1 Application Loaded
0 1 0 1 0 0 Currently Loading the Boot Project
1 1 0 1 0 0 System Initialization in Progress
0 0 0 1 0 1 Application Loaded -with BPT Break Point(s) Set
0 0 0 0 1 1 Application Running Display Blank
0 0 0 1 1 1 Running with BPT Break Point in Debug
0 1 1 0 0 0 Recovery Mode * SW2-C = ON
1 0 0 1 0 0 Battery Fail
0 0 1 0 0 0 System Firmware XSUM error
1 0 0 0 0 0 Diagnostic Mode SW4-8 = OFF
1 1 0 0 0 0 Running Diagnostic
1 0 1 0 0 0 Error initializing application device
0 1 1 0 0 0 NPX Error Unit stopped
1 1 0 1 1 1 Waiting for Power-down After NMI
0 0 0 1 0 0 Factory defaults applied Flashed at startup
0 0 0 0 1 0 Waiting for Alt. WD Timer Control Point error
0 1 1 1 1 1 Waiting for updump
1 1 1 0 0 0 FLASH programming error
1 1 1 1 1 1 Unit crashed
* Not an actual Running Status Code - SW2-C should be OFF
2.5.2.3 Remote Upgrade of ControlWaveLP Firmware
It is possible to download system firmware into an unattended remote ControlWaveLP.
This function can only be accomplished if CPU Board Switch SW4-6 (associated with the
unit in question) is set in the ON position (factory default). The procedure for performing a